Backflow Prevention
Backflow Prevention Assembly Test And Certification Report
|
Every fire inspection form should have a checkoff to see if the backflow preventor was tested. If not refer to your plumbing water purveyor. (public works or private)
The test must be conducted by a licensed plumber in the state of Illinois who is also a Certified Cross Control Detector Inspector. |
||||||
|
ILLINOIS PLUMBING CODE (02/04) |
|||||||
|
77
ILLINOIS ADMINISTRATIVE CODE, PART 890 Tables M, N, O, P |
|||||||
|
NFPA 13 |
|||||||
| 7.5.3.2
Where the connection between the antifreeze system and the wet pipe system incorporates a backflow prevention device, piping and valves shall be installed as illustrated in Figure 7.5.3.2.
|
|||||||
| 8.15.1.1.3.2 Piping Installation
A listed backflow prevention device shall be considered a check valve, and an additional check valve shall not be required. FAQ Each source of water supply must have check valve to isolate the supplies from each other. In a fire situation, water flows from the highest pressure source. Fore example, consider a system supplied by a gravity tank, a city connection, and a fire department connection. The gravity tank has the highest pressure source. Initial flow would be from the gravity tank. If the tank's pressure dropped below that of the city connection, the tank's check valve would close and the supply would come from the city. When the fire department connected onto the system, the check valves in both automatic supplies would close and the supply would come through the fire department pumps via the fire department connection. |
|||||||
| 8.16.4.6 Backflow Devices
A.8.16.4.6 Where backflow prevention devices are installed, they should be in an accessible location to provide for service and maintenance. |
|||||||
|
16.2.5 Backflow Prevention Assemblies |
|||||||
|
16.2.5.1
The backflow prevention assembly shall be forward flow tested to ensure proper operation. |
|||||||
| 16.2.5.2
The minimum flow rate shall be the system demand, including hose stream demand where applicable. Backflow prevention assemblies are covered in 16.2.5.1 and 16.2.5.2. Additional information on the testing of backflow devices is provided in 8.16.4.6. Due to their affect on sprinkler systems, backflow prevention devices must be accounted for through hydraulic analysis and flow testing |
|||||||
|
|
|||||||
|
8.3.3.3.2 Connections Between Antifreeze System and Wet Pipe System with Backflow Prevention Device Installed. |
|||||||
|
8.3.3.3.2.1 Valves shall be provided as illustrated in Figure 8.3.3.3.2.1.
|
|||||||
| 8.3.3.3.2.2
An expansion chamber shall be provided as illustrated in Figure 8.3.3.3.2.1. |
|||||||
| 8.3.3.3.2.3
The expansion chamber shall be sized based on the minimum and maximum volume of the antifreeze solution over the life of the system. |
|||||||
|
|
For additional information go to:
